Troubleshooting
AL007 Excessive deviation of Speed command
Condition: difference between the command speed and the feedback speed
exceeds the allowable range set by P2.034.
Trigger condition
and cause
Cause:
1. A drastic change in the input Speed command.
2. Improper setting of P2.034 (Excessive deviation warning condition of Speed
command).
3. Incorrect wiring of the UVW and encoder cables.
1. Use the signal detector to check if the input analog voltage signal is normal.
If not, adjust the rate of change for input signals or enable the filter function.
Checking method
and corrective action
2.
Check if the value of P2.034 (Excessive deviation warning condition of Speed
command) is set properly.
3. Check if the wiring of the motor power cable and encoder cable is correct.
How to clear the
alarm?
DI.ARST
14
AL008 Abnormal pulse command
Trigger condition
and cause
Condition: the input frequency of the pulse command is over the allowable value
for the hardware interface.
Cause: the pulse command frequency is higher than the rated input frequency.
Checking method Use the scope to check if the input frequency is higher than the rated input
and corrective action frequency and correctly set the input pulse frequency.
How to clear the
alarm?
DI.ARST
AL009 Excessive deviation of Position command
Condition: difference between the command position and the feedback position
exceeds the allowable range set by P2.035.
Cause:
1. The maximum position deviation is set too low.
Trigger condition
and cause
2. Gain value is set too low.
3. Torque limit or speed limit is set too low.
4. Excessive external load.
5. Improper setting for the E-Gear ratio.
6. The power cable is loose.
7. The maximum speed limit is set too low.