Troubleshooting
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
14
AL005 Regeneration error
Condition: an error occurs during regeneration.
Cause:
Trigger condition
and cause
1. Incorrect selection of the regenerative resistor or no connection to an external
regenerative resistor.
2. P1.053 (Regenerative resistor capacity) is not set to 0 when the regenerative
resistor is not connected.
3. Incorrect parameter settings for P1.052 and P1.053.
1. Check the connection for the regenerative resistor, re-calculate the value for
the regenerative resistor, and correctly set the values of P1.052 and P1.053.
Checking method
If the issue persists, send your servo drive back to Delta.
and corrective action 2. Set P1.053 to 0 if not using a regenerative resistor.
3. Correctly set the regenerative resistor value (P1.052) and the regenerative
resistor capacity (P1.053).
How to clear the
alarm?
DI.ARST
AL006 Overload
Condition: overload of motor and servo drive.
Cause:
Trigger condition
and cause
1. The load is over the rated range and the servo drive is in a continuous
overload condition.
2. Improper parameter settings.
3. Incorrect motor wiring.
4. Encoder is in error.
1. Set P0.002 to 12 for monitoring if the average load rate [%] is continuously
over 100%. If so, increase the motor capacity or reduce the load. Refer to
Appendix A for Graph of load and operating time.
Checking method 2. Check if there is any mechanical vibration or the setting for acceleration or
and corrective action
deceleration is too drastic.
3. Check if the wiring of the motor power cable and encoder cable is correct.
4. Send the motor back to the distributor or contact Delta.
How to clear the
alarm?
DI.ARST
14-12