Troubleshooting
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
14
14.2 Causes and corrective actions
AL001 Overcurrent
Condition: main circuit current is greater than 1.5 times the maximum instantaneous
Trigger condition
and cause
current of the servo drive.
Cause:
1. The servo drive output is short-circuited.
2. Motor wiring is in error.
3. IGBT is abnormal.
1. Check the connection between the motor and servo drive and make sure that
the wire is not short-circuited. Do not expose the metal part of the wiring.
Check if you have followed the wiring sequence for connecting the motor to
Checking method
the servo drive as described in this manual.
and corrective action 2. If the temperature of the heat sink is abnormal, send your servo drive back to
the distributor or contact Delta. Check if the set value of the parameter is
much greater than the default. It is recommended that you reset the parameter
to the factory default setting and then modify the setting gradually.
How to clear the
alarm?
Cycle power on the servo drive.
AL002 Overvoltage
Trigger condition
and cause
Condition: main circuit voltage exceeds the rated value.
Cause:
1. The input voltage of the main circuit is higher than the allowable rated value.
2. Incorrect power input (incorrect power system).
3. Malfunction of the servo drive hardware.
4. Incorrect selection of the regenerative resistor or no connection to an external
regenerative resistor.
1. Use a voltmeter to check if the input voltage of the main circuit is within the
allowable rated value (refer to Appendix A Specifications) and check if the
power system complies with the specifications. Use the right voltage source or
connect the transformer and regulator in series to have the voltage be within
Checking method
the specified range.
and corrective action 2. If the alarm occurs when the input voltage of the main circuit measured by the
voltmeter is within the allowable rated value, send your servo drive back to the
distributor or contact Delta.
How to clear the
alarm?
3. Check the connection for the regenerative resistor, re-calculate the value for
the regenerative resistor, and correctly set the values of P1.052 and P1.053.
DI.ARST
14-10