EtherCAT Mode
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
13
Example:
To set the three PDOs, OD 6040h, OD 607Ah, and OD 6060h, in the first group of PDO,
the setting is as follows.
Mapping
parameter setting
for RxPDO
OD 1600h sub0
OD 1600h sub1
OD 1600h sub2
OD 1600h sub3
Note
Data
Description
3
Set 3 PDO mappings.
6040h
00h
10h
Mapping Controlword (6040h);
data length is 16-bit
607Ah
00h
20h
Mapping target position (607Ah);
data length is 32-bit
6060h
00h
08h
Mapping mode (6060h);
data length is 8-bit
The total length is 38h (56-bit) which meets the specification of less
than 64-bit.
Objects 1A00h - 1A03h: Transmit PDO mapping parameter
Index
Name
Object code
Data type
Access
Note
1A00h, 1A01h, 1A02h, 1A03h
Transmit PDO mapping parameter
RECORD
PDO mapping
RW
The total length of objects in a group of PDO cannot
exceed 64 bits.
Sub-index
Description
Data type
Access
PDO mapping
Setting range
Default
0
Number of PDO mappings
UNSIGNED8
RW
No
0: disable
1 - 8: set the number of PDO mapping and enable
the function
0
Sub-index
Description
Data type
Access
PDO mapping
Setting range
Default
1 - 8
Specify the 1st (to 8th) object and its content to be
mapped
UNSIGNED32
RW
No
UNSIGNED32
0
Format of this object: (High word h) DCBA; (Low word L) UZYX
DCBA
Bit 16 - Bit 31
Object index
YX
Bit 0 - Bit 7
Object data length
UZ
Bit 8 - Bit 15
Object sub-index
13-52