CANopen Mode
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
12
Bit
Bit 12 - Bit 13
Bit 14
Bit 15
Status
-
-
Positive limit
Negative limit
Positive limit
Negative limit
Description
These bits are individually
defined according to the
operation mode, as shown in
the following table.
-
-
Bit 0 - Bit 6: current status of the servo drive.
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Description
0
-
-
0
0
0
0 Not ready to switch on.
1
-
-
0
0
0
0 Switch on disabled.
0
1
-
0
0
0
1 Ready to switch on.
0
1
-
0
0
1
1 Switched on.
0
1
-
0
1
1
1 Operation enabled (Servo On).
0
0
-
0
1
1
1 Quick stop active.
0
-
-
1
1
1
1 Fault reaction active.
0
-
-
1
0
0
0 Servo fault (servo switches to Servo Off).
Note: 0 indicates the bit is off, 1 indicates the bit is on, and - indicates the bit is invalid.
Bit 12 - Bit 13: current status of the servo drive.
Definition in each operation mode
Bit
Profile Position
mode
Homing mode
Interpolated Profile Velocity Profile Torque
Position mode
mode
mode
Set-point
Bit 12
acknowledge
(servo received the
Homing is
complete
Interpolation
in operation
Zero speed
-
command signal)
Bit 13 Following error Homing error
-
-
-
Note: - indicates the bit is invalid.
Object 605Bh: Shutdown option code
Index
Name
Object code
Data type
Access
PDO mapping
Setting range
Default
605Bh
Shutdown option code
VAR
INTEGER16
RW
Yes
INTEGER16
0
Object function:
Set to 0: when Servo Off, the dynamic brake has no effect, so the motor runs freely and the
machine stops only by friction.
Set to -1: when Servo Off, the servo stops with the operation of the dynamic brake.
Note: when P3.012.Z is set to 1, the non-volatile setting for this object is enabled.
12-58