ACD320 user manual
Parameter Description
Relationship betweenmulti-speed and MI1MI2MI3 terminals:
MI1
MI2
Current segment of
MI3
multi-speed control
OFF
OFF
OFF
Multi-Speed 0
ON
OFF
OFF
Multi-Speed 1
OFF
ON
OFF
Multi-Speed 2
ON
ON
OFF
Multi-Speed 3
OFF
OFF
ON
Multi-Speed 4
ON
OFF
ON
Multi-Speed 5
OFF
ON
ON
Multi-Speed 6
ON
ON
ON
Multi-Speed 7
6.6 F5 Protection Parameters
Function Code
Name
Setting Range
Default
Value
0: Noprotection
Motor Overload
1: normal motor
F5.00
1
Protection Option
2: Variable
Frequencymotor
0: no protection. There is nomotor overloading protection characteristic (caution to use),and
thereby the inverter has no protection to the overloaded motor.
1: normalmotor (with low speed compensation).As generalmotor has a poor heat emission at
low speed, the relevant electronic thermal protection should be regulated properly.The low speed
compensation characteristic herementioned is to switch down the overloading protection
threshold for themotor with an operation frequency lower than 30 Hz.
2:Variable frequencymotor (without lowspeed compensation).As the heat emission of
special variable frequency motor is not affected by speed, it is not required to regulate the
protection value for lowspeed operation.
Function Code
Name
Setting Range
Default
Value
F5.01
Motor Overload
Protection Current
20.0% 120.0%(motor
rated current)
100.0%
- 92-
    "