ACD320 user manual
Parameter Description
F4.11
Fault auto-reset times
03
0
Interval time setting of
F4.12
0.1100.0s
1.0s
automatic resetting fault
Fault auto-reset times: used to set the auto-reset times when inverter chooses fault auto-reset.
If this value is exceeded, inverterwill wait for trouble shooting.
Interval time setting of fault auto-reset: chose the interval time between fault occurring and
automatic resetting actuated.
Function Code Name
Setting Range
Default
Value
F4.13
FDT level detection value 0.00F0.04
50.00Hz
F4.14
FDT delay detection value 0.0100.0%(FDTlevel) 5.0%
Set output frequency detection value and the delay value of output action dismissed, as
shown by following figure:
Fig.6-16 FDT LevelDiagram
Function Code
Name
Setting Range
Default
Value
F4.15
Frequency reaching
0.0100.0%(maximum
0.0%
detection range
frequency)
When the inverter output frequency reaches the set frequency value, this function can
regulate its detect ion range value, as shown by following figure:
- 85-
    "