ACD320 user manual
Parameter Description
Simple PLC run for a After simple PLC run for a cycle, output impulse signal of
21
cycle
500ms.
22~24
Reserved
Reserved
Function Code
Name
Setting Range
Default
Value
F2.22
AO1 output selection
0~10
0
The standard analog output is 0-20mA(or 0-10V). Current or voltage output can be selected
by Jumper S2. Its corresponding value range is shown as following table:
Setting Value
Function
Range
0
Setting frequency 0-maximum output frequency
Operating
1
frequency
0-maximum output frequency
2
Output current
0-double rated inverter current
3
Output voltage
0-1.5 times rated inverter voltage
4
Motor speed
0-double rated motor speed
5
Output power
0-double rated power
6
Output torque
0-double rated motor current
7
Analog AVI input 0~ 10V/0~20mA
8
Analog ACI input 0~ 10V/0~20mA
9~10
Reserved
Reserved
Function Code
Name
Setting Range
Default
Value
F2.23
F2.24
F2.25
AO1 Lower limit
Lower limit corresponding
AO1 output
AO1 Upper limit
0.0%~100.0%
0.00V~10.00V
0.0%~100.0%
0.0%
0.00V
100.0%
Upper limit corresponding
F2.26
AO1 output
0.00V~10.00V
10.00V
Above function codes define the relationship between output value and analog output
corresponding output value.When the output value exceeds the maximum output or the minimum
output range, the beyond portion should be calculated with maximum output or minimum output.