ACD320 user manual
Parameter Description
increasing/decreasing clear, and the given frequency will return to that the frequency
set clear temporarily command channel has given, while it will to the frequency value
after the increasing/decreasing set.
31
Reserved
Function Code
Name
Setting Range
Default
Value
0: two-wirecontrol 1
F2.07
Terminal cont rol
1: two-wirecontrol2
0
mode
2: three-wire control 1
3: three-wire control 2
This parameter defines four different control modes which controls the inverter operation
through external terminals.
0: Two-wire type control, integrate Enable with direction. This mode is the most often used
two-wire controlmode. The motor forward and reverse operations are determined by the defined
FWD and REV terminal command.
Operation
K1
K2
Command
OFF
OFF
STOP
ON
OFF
FWD
OFF
ON
REV
ON
ON
STOP
Fig. 6-8 Two-wire operation mode 1
1: Two-wire control, separateEnable fromdirection.When thismode is used, the defined
FWDis enable terminal. The direction is determined by the defined REVstate.
K1
K2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Fig. 6-9 Two-wire operation mode 2
- 72-
Operation
Command
STOP
FWD
STOP
REV