- You are here:
- AM.CO.ZABuythisCNC Utilities Homepage
- EasyRoute-CNC-Router
- Component Manuals
- KR Inverter ACD320 Series Manual.pdf
- Page 113 of 160
ACD320 user manual
3
4
5
6
7
8
9~10
Output voltage
Running speed
Output power
Output torque
Analog value AVI
input
Analog value ACI
input
Reserved
Parameter Description
motor
0 to 150% of the rated voltage of
the motor
0 to 200% of the rated running
speedof the motor
0 to 200% rated power of the motor
0 to 200% of the rated current of the
motor
0~ 10V/0~20mA
0~ 10V/0~20mA
Reserved
Function Code
Name
Setting Range
Default
Value
F9.10
AO2 analog output lower
limit
0.0%~100.0%
0.0%
F9.11
AO2 lower limit
corresponding analog
0.00~10.00V
0.0%
F9.12
AO2 analog output upper
limit
0.0%~100.0%
100.0%
F9.13
AO2 upper limit
corresponding analog
0.00V~10.00V
10.00V
The above function code defines the relationship between the output value and the analog
output corresponding value, the part of the output value that exceeding the maximum or
minimum output setting scope will be calculated according to the maximum or minimum output.
When analog output is the current output, 1mA current is equivalent to the 0.5V voltage.
In different applications, 100% of analog output corresponding to the output values are
different, please refer to the specific description of each application part.
- 108-