ACD320 user manual
Parameter Description
F7.15
Water supply relay B1
26: The 1st pump of AC
26
fuctionG1-RCM
power
Water supply relay B1
27: The 2nd pump of
F7.16
27
fuctionB2-RCM
variable frequency
F7.17
Water supply relay B1
28: The 2nd pump of AC
28
fuctionG2-RCM
power
F7.18F7.20
Reserved
Reserved
F7.21
Sleep detection frequency
0the maximum
0.00
frequency
F7.22
Sleep detection delay
0999.9s
0.0
When feedback pressure is larger than high pressure and reach detecting point(F7.12),
inverter will stop outputting, turn into sleeping state immediatelyand display “EoPP”.
When output frequency is lower then that F7.21 have set and keep F7.22 delay, the inverter
will stop output , turn into sleeping state, and display “EoPP”.
Remark:When any parameter is 0, the sleeping function is ineffective.
Function Code
Name
Setting Range
Default
Value
F7.23
Revival pressure
1100.0%
0.0
F7.24
Revival detection delay
0999.9s
0.0
In positive acting mode, when feedback value is lower than the set value of F7.23 and keep
F7.24 delay, the inverter relieve sleeping status and start to output again.
Remark:When any parameter is 0, revival function is ineffective.
Function Code
Name
Setting Range
Default
Value
F7.25
Water-lack detection
0999.9s
0.0
delay.
When output frequency is at the upper limit, the inverter stop to output and display “U-26”
alarm if the feedback value haven’t arrived the specified value and keep F7.25 delay.
Function Code
Name
Setting Range
Default
Value
F7.26
PID adjusting range
050.0
10.0
Set the PID effective tuning range, improve the controllability of motor acceleration and
deceleration outside the rangethe acceleration and deceleration time is subject to F0.08/F0.09
and the time within the range can be seen by setting parameters F9.02, F9.03.
- 100-
    "