ACD320 user manual
Parameter Description
When this parameter is set to be 0.0s, this function is invalid.
When this function is valid, if the interval time between two communications exceeds
communication overtime time, it will cause communication fault (U-16).
Normallyit is set to be ineffective. Cmmunication status can be monitored by setting the
parameter in continuous communication system.
Function Code
Name
Setting Range
Default
Value
F6.05
Communication er ror
0: Alarmand free run
1
measure
stop
1: No alarm and keep
running
2 : No alarm and stop
according to stop mode
(by communication)
3: No alarm and stop
according to stop mode
(by all control mode)
The inverter can shield the failure alarm and stop to keep running by setting protecting
action selection in abnormal communication condition.
Function Code
Name
Setting Range
Default
Value
F6.06
0: Response when write
Response measure
0
1: No response when write
When this parameter is set to be 0, Response when write.
When this parameter is set to be 1, No Response whenwrite.This function can improve
communiation speed.
6.8 F7 Senior Function Parameters
Function Code
Name
Setting Range
Default
Value
0: One driving two circularly
The choice of
water supply mode is ineffective
F7.00
constant pressure
0
1: One driving two circularly
water supply mode
water supply mode is ineffective
When one driving two water supply circle mode is effectivethe water supply card is a
- 98-
    "