Figure 11 Schematic diagram of eleven tracks of return to zero mode
Return to zero mode12
WhenP03-61 = 12, select return to zero mode 12:
Take the CW direction end of HS limit as reference point, and the first Z signal in CCW
direction as zero point.
The starting position is at theCCW direction side of HS limit: the motor firstly moves in
CCW direction at the speed of P03-65 returning to the mechanical origin; after CCW limit is activated,
the motor decelerates to move in CW direction; after HS limit is activated and then left, the motor
moves in CCW direction at low speed; after HS limit is activated, the first Z signal is the zero
origin;
The starting position is onHS limit: the motor runs at low speed in CW direction according
to P03-66. After leaving HS limit, the motor runs at low speed in CCW direction. After activating
HS limit, the first Z signal is the zero return origin;
The starting position is atthe CW direction side of HS limit: the motor first moves in CCW
direction at the speed of P03-65 returning to the mechanical origin, and after activating HS limit,
the first Z signal is returning to the zero origin;