11.1.2 Basic setting and description of MODBUS-based
communication servo
The system using absolute value encoder shall initialize the encoder battery alarm and rotation number data when it
is put into use (F06.En0 clear encoder alarm; F07.En1 absolute encoder multi-turn value clearing). Because the
motor body and the battery are disconnected before the first use, the encoder will have no battery alarm and loop
memory function.
parameter
code
Name
P00-23
slave address
P00-24.0
Modbus communication baud
rate
P00-24.1
check mode
Note:
Setting range: 0-255, default 1
Set according to equipment requirements
Setting range: 0-7, default 2
02400
14800
29600
319200
438400
557600
6115200
725600
Setting range: 0-3, default 0
0: no check, 2 stop bits
1: even parity, 1 stop bit
2: Odd parity, 1 stop bit
3: No check, 1 stop bit
11. 1.3Absolute data address based on MODBUS
communication
Content
Address: decimal
Absolute encoder position within one
2126-2127
turn
Notes
Single-turn value range: 0-8388608