Fault alarm reason
Overtemperature warning set too
low
Drive Temperature Abnormal
Fault alarm check
Confirm whether parameter P00-42
is set properly
Drive temperature monitoring can
be performed via d24.Ath in
monitor mode
disposal measures
Set P00-42 correctly
improve heat dissipation condition
of that drive
Drive temperature still alarms
under normal conditions, replace
the drive
A.920: Regeneration Overload Warning
Fault alarm reason
Wrong selection of regenerative
resistor or no external
regenerative resistor
Incorrect parameter setting
Fault alarm check
Check the connection condition of
the regenerative resistor and
whether the resistance and power of
the regenerative resistor are suitable
Confirm whether the parameters
P00-30~P00-35 are correct
disposal measures
Select the appropriate regenerative
resistor
Set parameter values correctly
A.930: ABSOLUTE ENCODER BATTERY FAULT
Fault alarm reason
ABSOLUTE ENCODER
BATTERY FAULT
Fault alarm check
Check the voltage of the external
battery of the encoder and confirm
that it is higher than 3.0V
disposal measures
Battery voltage is lower than 3.0V,
replace battery
Clear with command F06.En0 if
higher
A.941: Parameter changes require power off and restart to take effect
Fault alarm reason
After modifying the parameters,
the parameters shall take effect
after re-powering on
Fault alarm check
After modifying the parameters, the
parameters shall take effect after
re-powering on
disposal measures
Power off and restart
A.960: Input Terminal Duplicate Definition
Fault alarm reason
Input terminal duplicate definition
Fault alarm check
Check whether there is signal input
at the external input port and
whether the relevant parameters of
disposal measures
Correctly set relevant parameters