Shenzhen Just Motion Control electromechanics co., ltd
0755-26509689
Fault alarm reason
FN function cannot be executed
when servo is ON
Fault alarm check
FN function cannot be executed
when servo is ON
disposal measures
Perform FN function with SV-OFF
A.910: Overload warning
Fault alarm reason
Fault alarm check
disposal measures
overload warning
Improper setting of control system
parameters
Motor wiring error
Can be monitored via d13.oL. in
monitor mode
1. Whether the mechanical system
is installed
2. Acceleration setting constant is
too fast
3. Whether the gain parameters are
set correctly
Check U, V, W wiring
Increase P00-51 (overload warning
value) appropriately
1. Adjust the gain of control loop
2. Increase the acceleration and
deceleration time
correct wiring
A.911: Vibration Warning
Fault alarm reason
Abnormal vibration of motor
speed detected
The value of the moment of
inertia ratio (P01-04) is larger than
the actual value or varies greatly
Fault alarm check
Confirm the abnormal sound of the
motor and the speed and torque
waveform during operation.
Confirm the load moment of inertia
ratio
disposal measures
Reduce the motor speed.
Or reduce the speed loop gain
(P02-10)
Set the appropriate ratio of moment
of inertia (P01-04)
P01-10 can be set to turn off the
alarm
A.912: Abnormal Control Board Temperature
Fault alarm reason
Abnormal temperature of control
board
Fault alarm check
Check Drive Temperature
Does the cooling fan work properly
disposal measures
improve heat dissipation condition
of that drive
Drive temperature still alarms
under normal conditions, replace
the drive
A.913: Abnormal Drive Temperature
167