E.645: Bus Encoder Multiturn Overflow Fault
Fault alarm reason
Bus encoder turns out of range
Fault alarm check
The number of turns can be
monitored through the monitoring
mode d21.ASH, and the multi-turn
absolute motor cannot rotate in one
direction for a long time.
disposal measures
Alarm can be cleared via F06.EN0
Clear the multi-turn value using the
command F07.En1
Alarm can be switched off via
parameter P00-07
E.646: Encoder communication failure
Fault alarm reason
Encoder communication failure
Fault alarm check
Check Encoder
disposal measures
Correct installation of encoder
E.649: Encoder Communication CRC Failure
Fault alarm reason
Encoder communication CRC
failure
Fault alarm check
Check Encoder
disposal measures
Correct installation of encoder
A.900: Excessive positional deviation
Fault alarm reason
Excessive position deviation
warning
Gain value set too small
Internal torque limit set too small
Fault alarm check
Confirm parameter setting of
P03-15/P03-30 (excessive position
deviation setting)
Confirm whether the gain
parameters are set reasonably
Confirm internal torque limit value
Excessive external load
Check external load
disposal measures
Increase P03-15/P03-30 (excessive
position deviation setting) setting
Readjust the gain class parameters
correctly
Readjust the internal torque limit
correctly
Reduce the load or replace the
high-power motor
A.901: Excessive position deviation when servo is ON
Fault alarm reason
Excessive position deviation when
servo is ON
Pulse command frequency is too
high when servo is ON
Fault alarm check
Confirm P03-31/P03-33 parameter
setting
Pulse command frequency is too
high when servo is ON
disposal measures
Increase P03-31/P03-33 setpoint
Reduce the pulse command
frequency when servo is ON
A.905: FN function cannot be executed when servo is ON