failure
E.621: Encoder built-in data mismatch
Fault alarm reason
Encoder read/write exception
Abnormal motor parameter setting
Fault alarm check
Check the encoder wiring.
Correctly set the motor parameters
of P00-00~ P00-19
disposal measures
correct wiring
Set parameters correctly
E.622: Encoder built-in data check error
Fault alarm reason
Encoder built-in data verification
error
Fault alarm check
Check Encoder Wiring
Verify encoder shield wire is
properly connected
disposal measures
If the connection is normal, return
the drive to the factory for repair
E.641: Encoder overheating (encoder internal)
Fault alarm reason
Encoder overheating (inside
encoder)
Fault alarm check
Check encoder temperature
disposal measures
If the temperature is normal, the
alarm can be cleared by F06.EN0
Modify parameter P00-07.2 Alarm
Off
E.643: Bus Encoder Battery Failure
Fault alarm reason
Low external battery voltage
when bus encoder is set to
multi-turn absolute value
Fault alarm check
Check the voltage of the external
battery of the encoder and confirm
that it is higher than 3.0V
disposal measures
When the battery voltage is lower
than 3.0V, replace the battery.
Alarm cleared above 3V using
auxiliary function F06.EN0
Alarm can be switched off via
parameter P00-07
E.644: Bus Encoder Multi-turn Exception
Fault alarm reason
Bus encoder turns out of range
Fault alarm check
The number of turns can be
monitored through the monitoring
mode d21.ASH, and the multi-turn
absolute motor cannot rotate in one
direction for a long time.
disposal measures
Clear the multi-turn value using the
command F07.En1