Shenzhen Just Motion Control electromechanics co., ltd
0755-26509689
motor is started
P00-50 Parameter setting is
unreasonable
Drive hardware failure
binding
Check P00-50 parameter value
Set P00-50 parameters correctly
Confirm that the mechanical part is
normal and still alarm
Please send it back to the dealer or
the original factory for maintenance
E.412: Sustained overload
Fault alarm reason
Continuous use beyond the drive
rated load
Improper setting of control
system parameters
Motor wiring error
Fault alarm check
Can be monitored via d13.oL. in
monitor mode
1. Whether the mechanical system
is installed
2. Acceleration setting constant is
too fast
3. Whether the gain parameters are
set correctly
Check U, V, W wiring
disposal measures
Change to a higher power motor or
reduce the load
1. Adjust the gain of control loop
2. Acceleration and deceleration
setting time slows down
correct wiring
E.420: Overspeed
Fault alarm reason
Input speed command too high
Unreasonable setting of overspeed
judgment parameters
Fault alarm check
Check whether the input signal is
normal
Check whether P04-05 (overspeed
alarm value) is set properly
disposal measures
Adjust the frequency of the input
signal
Set P04-05 correctly (overspeed
alarm value)
E.421: Out of control detection
Fault alarm reason
Motor power lines U,V,W wiring
error
Incorrect motor parameter setting
Fault alarm check
Check wiring
disposal measures
correct wiring
Check P00-05; and whether the
encoder parameters are set correctly
Set parameters correctly
Set P00-46.1 to 0 to close runaway
detection
E.430: Regeneration Abnormal
161