Shenzhen Just Motion Control electromechanics co., ltd
0755-26509689
E.400: Power cord phase loss
Fault alarm reason
Main circuit input power line
phase loss
Fault alarm check
Check whether the main circuit
input L1,L2 and L3 are connected
disposal measures
Make sure that the wiring is correct
and that the correct voltage source
or voltage regulator is used in
series
P00-39.0 Open phase alarm can be
turned off
E.401: Undervoltage
Fault alarm reason
The input voltage of the main
circuit is lower than the rated
voltage value or there is no input
voltage
Fault alarm check
Check whether the main circuit
input L1,L2,L3 wiring is correct,
and the voltage value is how many
volts. The bus voltage can be
monitored via d23.dcp
disposal measures
Make sure that the wiring is correct
and that the correct voltage source
or series regulator is used
P00-52 Alarm threshold can be
modified
E.402: Overvoltage
Fault alarm reason
Main circuit input voltage is too
high
The regenerative resistor is not
connected or the type selection of
the regenerative resistor is
incorrect
Incorrect parameter settings
Drive hardware failure
Fault alarm check
Use voltmeter to test whether the
input voltage of main circuit is
correct
Check that the appropriate
regeneration resistor is connected
disposal measures
Use the correct voltage source or
series regulator
Properly connected matching
regenerative resistors
Confirm that the parameter settings
of P00-30~P00-34 are consistent
with the resistor connection mode
Overvoltage alarm still occurs
when the input voltage is
determined to be correct
Correct setting of parameters and
external regenerative resistance
Please send it back to the dealer or
the original factory for maintenance
E.410: Instantaneous overload
Fault alarm reason
The machine is stuck when the
Fault alarm check
Check mechanical connections for
disposal measures
Adjust the mechanical structure
160