Fault alarm reason
U,V,W short to earth PE
Fault alarm check
Check for correct wiring
Try to remove the motor power line
disposal measures
Correct wiring, replace motor wire
and motor.
If it persists, replace the drive
E.069: FPGA Clock Exception
Fault alarm reason
FPGA clock exception
Fault alarm check
FPGA clock exception
disposal measures
P00-47.1 Set 0 to turn off alarm
If it persists, replace the drive
E.071: U-phase current detection abnormality
Fault alarm reason
Abnormal sampling data of
current sensing device
Fault alarm check
Check whether the UVW wiring is
correct and the connection is
reliable
disposal measures
correct wiring
P00-46.2 Set 0 to turn off alarm
If it persists, replace the drive
E.072: Abnormal detection of phase W current
Fault alarm reason
Abnormal sampling data of
current sensing device
Fault alarm check
Check whether the UVW wiring is
correct and the connection is
reliable
disposal measures
correct wiring
P00-46.3 Set 0 to turn off alarm
If it persists, replace the drive
E.100: Abnormal parameter combination
Fault alarm reason
Parameter setting error
Fault alarm check
Check the set parameters
disposal measures
Set parameters correctly
If it always appears, initialize the
parameters
E.102: DI Port Assignment Exception
Fault alarm reason
At least 2 input ports have the
same function selection
Fault alarm check
Check input port function selection
parameters (P06-11, P06-12...)
disposal measures
Set parameters correctly
Perform parameter initialization
and power on again
E.106: Abnormal setting of frequency division pulse output
Fault alarm reason
Divided pulse output parameter
Fault alarm check
Check the divided pulse output
disposal measures
Correct setting of frequency
158