E.054: Operation Timeout
Fault alarm reason
operation timeout
Fault alarm check
Power back on
disposal measures
If it persists, replace the drive
E.060: Hardware mismatch error
Fault alarm reason
Hardware mismatch error
Fault alarm check
Perform factory initialization
(F10.INI)
disposal measures
If consistently, contact
manufacturer
E.061: Motor and drive combination anomaly
Fault alarm reason
The servo unit does not match the
servo motor model
Fault alarm check
Check whether the servo unit
supports the motor
disposal measures
Replace the servo unit matching the
motor
E.063: Overcurrent detection
Fault alarm reason
Short circuit between U,V and W
Damaged drive
Fault alarm check
Is there a short circuit in the U,V,W
wiring
Is there a short circuit between B 1
and B 3
Disconnect the U,V,W cables on the
drive and enable the drive
disposal measures
correct wiring
If there is no alarm, check the
power line and motor for short
circuit
If the U,V,W connections are
disconnected and the startup drive
still alarms, replace the drive
E.064: Motor overcurrent detection
Fault alarm reason
Short circuit between U,V and W
Damaged drive
Fault alarm check
Is there a short circuit in the U,V,W
wiring
Is there a short circuit between B 1
and B 3
Disconnect the U,V,W cables on the
drive and enable the drive
disposal measures
correct wiring
If there is no alarm, check the
power line and motor for short
circuit
If the U,V,W connections are
disconnected and the startup drive
still alarms, replace the drive
E.068: Driver DC Bus Overcurrent Detection