P03-34
moving average time
Position command
first-order low-pass
filter time parameter
Denominator of the
number of divided
output pulses
Set the time constant of the position command smoothing filter,
moving average filter.
Setting range: 0-65535 Unit: 0.1ms
Sets the time constant of the position command smoothing filter, a
first-order low-pass filter.
Setting range:0-1073741823
When P03-23 is equal to 0, the frequency division pulse number
=P03-25*4 ; When P03-23 is not equal to 0, the number of divided
pulses =2^23*P03-25/P03-23.
Frequency division
output pulse number
Frequency division
0 output pulse phase
sequence inversion
Excessive position
deviation warning value
Excessive servo ON
position deviation alarm
value
Servo ON position
deviation excessive
warning value
overshoot detection
value
Setting range: 0-65535
Set the absolute value of the motor rotation, A, B frequency pulse
output quantity.
For example, if the setting value is 2500, the A and B signals output
2500 pulses each time the motor rotates one turn
is use for adjusting that phase sequence of the frequency division
output pulse
0: Normal.
1: Direction reversed
Setting range:0-100 Unit: %
Excessive position deviation warning value =P03-30 set value
*P03-15, warning occurs when the set value is exceeded A.900
Unit: Command UnitSetting Range: 0-1073741823
Set the pulse number of allowable deviation when servo is ON, if it
exceeds the set value, it will alarm E.503, and it will not be detected
when it is set to 0
Setting range:0-100 Unit: %
Excessive servo ON position deviation warning value = set value
*P03-31, warning A.901 occurs when the set value is exceeded
Setting range:0-100 Unit: %
Overshoot detection threshold = P03-34* P03-06.