Shenzhen Just Motion Control electromechanics co., ltd
0755-26509689
P00-55
P00-56
overload reference
value
Motor overload time
percentage
Setting range: 50-200 units: %
Set the initial threshold of the overload alarm curve, and when it is lower
than the reference value, the motor can run for a long time without
triggering the overload alarm.
Setting range: 10-100 units: %
Set overload protection time curve percentage
8.2.2 P01-xx Main Control Parameters
Param
Code
P01-00
Name
direction of
rotation
P01-01
Control mode
setting
Note:
Setting range: 0-1
0: counterclockwise is positive direction
1: Clockwise is positive direction
Setting range: 0-5
0: Position control mode
1: Speed control mode
2: Torque control mode
3: Speed and torque control mode. To switch using one of the external
input ports in CN1, set the selected DI portinput port function selection
to 5 (control mode switching). The control mode can be switched by
controlling the logic state of the port.
terminal logic
control mode
effective
velocity mode
invalid
torque mode
4: Position and speed control mode. To switch using one of the external
input ports in CN1, set the selected DI portinput port function selection
to 5 (control mode switching). The control mode can be switched by
117