P00-24
P00-24
P00-26
P00-30
P00-31
P00-32
P00-33
Slave ID setting
Modbus
0 communication baud
rate
485 communication
1
parity check mode
Modbus
communication
response delay
Braking resistor
setting
Power of external
braking resistor
Resistance value of
external braking
resistor
Built-in braking
resistance power
For example, when the customer needs to drive and display the motor
speed d08.F.SP at power-on, the parameter is set to 8
Setting range: 0-255, default 1
Slave ID setting during Modbus communication
Setting range: 0-7, default 2
0:2400
1:4800
2:9600
3:19200
4:38400
5:57600
6:115200
7:256000
Set range 0-3, default 0
0: no check, 2 stop bits
1: even parity, 1 stop bit
2: Odd parity, 1 stop bit
3: No check, 1 stop bit
Setting range: 0-100, unit. 01 mSDefault 0
When the parameter is set to 0, the response is made according to the
standard communication. When the parameter is set to have a value, the
response time of Modbus communication is made according to the set
time
Setting range: 0-2
0: No regenerative resistor used
1: Use built-in regenerative resistor
2: Use external regenerative resistor
Setting range: 1-65535, unit: 1W
Set correctly according to the external braking resistance power, such as:
Set to 40, resistor power is 40W
Setting range: 1-65535, unit: 0.1 ohm
Set correctly according to the resistance value of the external braking
resistor
Setting range: 1-65535, unit: 1W
Set the correct power according to the built-in braking resistor, e.g.: Set to
40, resistor power is 40W
114