Chapter 5 Parameters|VFD-B Series
Group 3: Output Function Parameters
03 - 00 Multi-function Output Relay (RA1, RB1, RC1)
03 - 01 Multi-function Output Terminal MO1
03 - 02 Multi-function Output Terminal MO2
03 - 03 Multi-function Output Terminal MO3
Factory Setting: 08
Factory Setting: 01
Factory Setting: 02
Factory Setting: 20
Settings
Function
Description
00 No Function
Active when there is an output from the drive or RUN
01 AC Drive Operational
command is “ON”.
Master Frequency
02
Attained
Active when the AC motor drive reaches the output
frequency setting.
03 Zero Speed
Active when Command Frequency is lower than the
Minimum Output Frequency.
Active as long as over-torque is detected. (Refer to Pr.06-03
04 Over-Torque Detection
~ Pr.06-05)
Baseblock (B.B.)
05
Indication
Active when the output of the AC motor drive is shut off
during baseblock. Base block can be forced by Multi-function
input (setting 9 or 10).
06 Low-Voltage Indication Active when low voltage(Lv) is detected.
Operation Mode
07
Indication
Active when operation command is controlled by external
terminal.
08 Fault Indication
Active when faults occur (oc, ov, oH, oL, oL1, EF, cF3, HPF,
ocA, ocd, ocn, GFF).
Desired Frequency
09
Attained 1
Active when the desired frequency (Pr.03-04) is attained.
10 PLC Program Running Active when PLC Program is running.
PLC Program Step
11
Completed
Active for 0.5 sec each time the multi-step speed is attained.
Active for 0.5 sec when the PLC program cycle has
12 PLC Program Completed
completed
13 PLC Operation Paused Active when PLC operation is paused.