Chapter 5 Parameters|VFD-B Series
FWD-DCM (close)
ON
OFF
Pr.02-01=0
RUN
RUN
STOP
STOP
output frequency
Pr.02-06=2 or 3
Change operation
command source
Pr.02-01=1 or 2
This action will follow FWD/DCM
or REV/DCM status
(ON is close/OFF is open)
output frequency
Pr.02-06=0 or 1
When the operation command source isn’t from the external terminals, independently from
whether the AC motor drive runs or stops, the AC motor drive will operate according to Pr.02-
06 if the two conditions below are both met.
1. When operation command source is changed to external terminal (Pr.02-01=1 or 2, Pr.02-
14=1 or 2)
2. The status of terminal and AC motor drive is different.
And the operation of the AC motor drive will be:
1. When setting 0 or 1, the status of AC motor drive is not changed by the terminal status.
2. When setting 2 or 3, the status of AC motor drive is changed by the terminal status.
FWD-DCM (close)
ON
OFF ON
power is applied
OFF
ON
output frequency
Pr.02-06=0 or 2
it will run
output frequency
Pr.02-06=1 or 3
it won't run
when power is applied
It needs to received a run command
after previous command is cancelled
The Line Start Lockout feature does not guarantee that the motor will never start under this
condition. It is possible the motor may be set in motion by a malfunctioning switch.