02- 06 Line Start Lockout
Settings
00
01
02
03
Chapter 5 Parameters|VFD-B Series
Factory Setting: 00
Disable. Operation status is not changed even if operation
command source Pr.02-01 and/or Pr.02-14 is changed.
Enable. Operation status is not changed even if operation command
source Pr.02-01 and/or Pr.02-14 is changed.
Disable. Operation status will change if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
Enable. Operation status will change if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
This parameter determines the response of the drive when power is on and the operation
command source is changed.
Pr.02-06 Start lockout (Run when power is ON)
0
Disable (AC motor drive will run)
1
Enable (AC motor drive won’t run)
2
Disable (AC motor drive will run)
3
Enable (AC motor drive won’t run)
Operation status when operation
command source is changed
Keep previous status
Keep previous status
Change according to the new
operation command source
Change according to the new
operation command source
When the operation command source is from an external terminal and operation command is
ON (FWD/REV-DCM=close), the AC motor drive will operate according to Pr.02-06 after
power is applied. <For terminals FWD and REV only>
1. When Pr.02-06 is set to 0 or 2, AC motor drive will run immediately.
2. When Pr.02-06 is set to 1 or 3, AC motor drive will remain stopped until operation
command is received after previous operation command is cancelled.
Revision July 2008, BE16, SW V4.08 & V5.00
5-39