Chapter 5 Parameters|VFD-B Series
02 - 04 Motor Direction Control
Settings
00 Enable Forward/Reverse operation
01 Disable Reverse operation
02 Disabled Forward operation
Factory Setting: 00
The parameter determines the AC motor drive direction of rotation. See Chapter 2 for definition
of direction of rotation.
02 - 05 2-wire/ 3-wire Operation Control Modes
Settings
00 2-wire: FWD/STOP, REV/STOP
01 2-wire: FWD/REV, RUN/STOP
02 3-wire Operation
There are three different types of control modes:
Factory Setting: 00
02-05
External Terminal
2-wire
FWD/STOP
00
FWD /STOP
REV / STOP
REV/STOP
FWD:("OPEN":STOP)
("CLOSE":FWD)
REV:("OPEN": STOP)
("CLOSE": REV)
DCM
VFD-B
2-wire
RUN/STOP
01
FWD/ REV
RUN / STOP
FWD/REV
FWD:("OPEN":STOP)
("CLOSE":RUN)
REV:("OPEN": FWD)
("CLOSE": REV)
DCM
VFD-B
STOP RUN
FWD:("CLOSE":RUN)
EF: ("OPEN":STOP)
02
3-wire
REV:("OPEN": FWD)
REV/FWD
("CLOSE": REV)
DCM
VFD-B
5-38
Revision July 2008, BE16, SW V4.08 & V5.00