Chapter 5 Parameters|VFD-B Series
1-08
Voltage
Output Frequency
Lower Limit
1-02
Maximum
Output
Voltage
1-07
Output Frequency
Upper Limit
1-04
Mid-point
Voltage
1-06
Minimum
Output
1-05
Voltage
Minimum
Output
Freq.
The limit of
Output
Frequency
Frequency
1-03
Mid-point
Freq.
1-01
Maximum Voltage
Frequency
(Base Frequency)
1-00
Maximum
Output
Frequency
V/f Curve
01 - 08 Output Frequency Lower Limit
Settings
0 to 100%
Unit: 1
Factory Setting: 0
The Upper/Lower Limits are to prevent operation errors and machine damage.
If the Output Frequency Upper Limit is 50Hz and the Maximum Output Frequency is 60Hz, the
Output Frequency will be limited to 50Hz.
If the Output Frequency Lower Limit is 10Hz, and the Minimum Output Frequency (Pr.01-05) is
set to 1.0Hz, then any Command Frequency between 1.0-10Hz will generate a 10Hz output
from the drive.
This parameter must be equal to or less than the Output Frequency Upper Limit (Pr.01-07).
The Output Frequency Lower Limit value = (Pr.01-00 * Pr.01-08) /100.
01 - 09 Acceleration Time 1 (Taccel 1)
01 - 10 Deceleration Time 1 (Tdecel 1)
01 - 11 Acceleration Time 2 (Taccel 2)
01 - 12 Deceleration Time 2 (Tdecel 2)
01 - 18 Acceleration Time 3 (Taccel 3)
01 - 19 Deceleration Time 3 (Tdecel 3)
01 - 20 Acceleration Time 4 (Taccel 4)
01 - 21 Deceleration Time 4 (Tdecel 4)
Settings 0.01 to 3600.0 sec
Factory setting for models of 30hp (22kW) and above is 60sec.
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Factory Setting: 10.0