Password Decode Flow Chart
00-08
Chapter 5 Parameters|VFD-B Series
00-07
Displays 00 when
entering correct
password into
Pr.00-07.
Correct Password
END
00-08
Incorrect Password
END
00-07
Displays 00 when
entering correct
password into
Pr.00-07.
3 chances to enter the correct
password.
1st time displays "01" if
password is incorrect.
2nd time displays "02", if
password is incorrect.
3rd time displays "P code"
(blinking)
If the password was entered
incorrectly after three tries,
the keypad will be locked.
Turn the power OFF/ON to
re-enter the password.
00 - 09 Control method
Settings
00 V/f control
01 V/f + PG Control
02 Vector Control
03 Vector + PG Control
Factory Setting: 00
This parameter determines the control method of the AC motor drive.
PG is encoder (Pulse Generator) feedback for which an option PG card is required.
00 - 10 Reserved
Revision July 2008, BE16, SW V4.08 & V5.00
5-27