Parameter Explanation
Settings
10-13
10-14
10-15
10-16
ASR (Auto Speed
Regulation) control 0.00 to 100.00 (0.00 disable)
(with PG only) (I)
Speed Control
Output Frequency 0.00 to 100.00 Hz
Limit
Sample time for
refreshing the
content of 210DH
0.01~1.00 seconds
and 210EH
Deviation Range of
PID Feedback Signal 0.00~100.00%
Error
Chapter 5 Parameters|VFD-B Series
Factory
Setting
Customer
1.00
10.00
0.10
100.00
Group 11 Fan & Pump Control Parameters
Parameter Explanation
Settings
11-00
11-01
V/f Curve Selection
Start-Up Frequency
of the Auxiliary
Motor
00: V/f curve determined by Pr.01-00 to
Pr.01-06
01: 1.5 power curve
02: 1.7 power curve
03: Square curve
04: Cube curve
0.00 to 400.00 Hz
11-02
Stop Frequency of
the Auxiliary Motor
0.00 to 400.00 Hz
11-03
11-04
11-05
Time Delay before
Starting the Auxiliary 0.0 to 3600.0 sec
Motor
Time Delay before
Stopping the
Auxiliary Motor
0.0 to 3600.0 sec
Sleep/Wake Up
Detection Time
0.0 ~6550.0 sec
11-06 Sleep Frequency 0.00~Fmax
11-07 Wakeup Frequency 0.00~Fmax
Factory
Setting
Customer
00
0.00
0.00
0.0
0.0
0.0
0.00
0.00
Revision July 2008, BE16, SW V4.08 & V5.00
5-17