Chapter 5 Parameters|VFD-B Series
Parameter Explanation
09-05 Reserved
09-06 Reserved
09-07 Response Delay
Time
00 ~ 200 msec
Settings
Factory
Setting
Customer
00
Group 10 PID Control Parameters
Parameter Explanation
Settings
10-00
Input terminal for
PID Feedback
10-01
Gain over PID
Detection value
00: Inhibit PID operation
01: Negative PID feedback from external
terminal (AVI) 0 to +10V
02: Negative PID feedback from external
terminal (ACI) 4 to 20mA
03: Positive PID feedback from external
terminal (AVI) 0 to +10V
04: Positive PID feedback from external
terminal (ACI) 4 to 20mA
0.00 to 10.00
10-02 Proportional Gain (P) 0.0 to 10.0
10-03
10-04
10-05
10-06
10-07
10-08
10-09
Integral Gain (I)
0.00 to 100.00 sec (0.00=disable)
Derivative Control
(D)
0.00 to 1.00 sec
Upper Bound for
Integral Control
00 to 100%
Primary Delay Filter
Time
0.0 to 2.5 sec
PID Output Freq
Limit
0 to 110%
Feedback Signal
Detection Time
0.0 to 3600.0 sec
Treatment of the
00: Warn and keep operation
Erroneous Feedback 01: Warn and RAMP to stop
Signals
02: Warn and COAST to stop
10-10 PG Pulse Range
10-11 PG Input
ASR (Auto Speed
10-12 Regulation) control
(with PG only) (P)
1 to 40000
00: Disable PG
01: Single phase
02: Forward / Counterclockwise rotation
03: Reverse / Clockwise rotation
0.0 to 10.0
Factory
Setting
Customer
00
1.00
1.0
1.00
0.00
100
0.0
100
60.0
00
600
00
1.0
5-16
Revision July 2008, BE16, SW V4.08 & V5.00