Parameter
08-14
08-15
08-16
08-17
08-18
Explanation
Auto Restart After
Fault
Auto Energy Saving
AVR Function
Software Brake
Level
Base-block Speed
Search
Settings
00 to 10 (00=disable)
Chapter 5 Parameters|VFD-B Series
Factory
Setting
Customer
00
00: Disable
01: Enable
00
00: AVR function enable
01: AVR function disable
00
02: AVR function disable for decel.
230V series: 370 to 430V
380
460V series: 740 to 860V
760
575V series: 925 to1075V
950
00: Speed search starts with last frequency
command
00
01: Starts with minimum output frequency
08-19
Speed Search
during Start-up
00: Speed search disable
01: Speed search enable
00
Speed Search
00: Setting frequency
08-20 Frequency during 01: Maximum operation frequency (01-00)
00
Start-up
08-21
Auto Reset Time at 00 to 60000 sec
Restart after Fault
600
Compensation
00~1000
08-22 Coefficient for Motor
00
Instability
Group 9 Communication Parameters
Parameter Explanation
Settings
09-00
09-01
09-02
09-03
09-04
Communication
Address
Transmission Speed
01 to 254
00: Baud rate 4800bps
01: Baud rate 9600bps
02: Baud rate 19200bps
Transmission Fault
Treatment
03: Baud rate 38400bps
00: Warn and keep operating
01: Warn and ramp to stop
02: Warn and coast to stop
03: No warning and keep operating
0.0 ~ 60.0 seconds
Time-out Detection
0.0: Disable
Communication
Protocol
00: 7,N,2 (Modbus, ASCII)
01: 7,E,1 (Modbus, ASCII)
02: 7,O,1 (Modbus, ASCII)
03: 8,N,2 (Modbus, RTU)
04: 8,E,1 (Modbus, RTU)
05: 8,O,1 (Modbus, RTU)
Factory
Setting
Customer
01
01
03
0.0
00
Revision July 2008, BE16, SW V4.08 & V5.00
5-15