Parameter Explanation
06-12
06-13
Under-Current
Detection Level
Under-Current
Detection Time
06-14
Under-Current
Detection Mode
06-15
Under-Current
Detection Restart
Delay Time (Lv)
06-16
User-Defined Low-
Voltage Detection
Level
06-17
06-18
User-Defined Low-
Voltage Detection
Time
Reserved
Settings
00~100% (00: Disabled)
0.1~ 3600.0 sec
Chapter 5 Parameters|VFD-B Series
Factory
Setting
Customer
00
10.0
00: Warn and keep operating
01: Warn and ramp to stop
02: Warn and coast to stop
00
03: Warn, after coast to stop, restart (delay
06-15 setting time)
1~600 Min.
10
00: Disabled
230V: 220 to 300VDC
00
460V: 440 to 600VDC
575V: 520 to 780VDC
0.1~ 3600.0 sec
0.5
Group 7 Motor Parameters
Parameter Explanation
Settings
07-00
07-01
07-02
07-03
07-04
07-05
Motor Rated Current
Motor No-Load
Current
Torque
Compensation
Slip Compensation
(Used without PG)
Number of Motor
Poles
Motor Parameters
Auto Tuning
30 to 120%
01 to 90%
0.0 to 10.0
0.00 to 3.00
02 to 10
00: Disable
01: Auto tuning R1
02: Auto tuning R1 + no-load test
07-06
07-07
07-08
07-09
07-10
07-11
Motor Line-to-line
Resistance R1
00~65535 mΩ
Reserved
Motor Rated Slip 0.00 to 20.00 Hz
Slip
Limit
Compensation
0 to 250%
Reserved
Reserved
Factory
Setting
Customer
100
40
0.0
0.00
04
00
00
3.00
200
Revision July 2008, BE16, SW V4.08 & V5.00
5-13