Parameter Explanation
04-10
04-11
Digital Terminal
Input Debouncing
Time
ACI Analog Input
Bias
04-12 ACI Bias Polarity
04-13 ACI Input Gain
04-14
ACI Negative Bias,
Reverse Motion
Enable/Disable
04-15
AUI Analog Input
Bias
04-16 AUI Bias Polarity
04-17
04-18
AUI Input Gain
AUI Negative Bias
Reverse Motion
Enable/Disable
04-19
04-20
04-21
04-22
04-23
04-24
04-25
AVI Analog Input
Delay
ACI Analog Input
Delay
AUI Analog Input
Delay
Analog Input
Frequency
Resolution
Gear Ratio for
Simple Index
Function
Index Angle for
Simple Index
Function
Deceleration Time
for Simple Index
Function
Chapter 5 Parameters|VFD-B Series
Settings
Factory
Setting
Customer
31: Source of second frequency command
enabled
32: Source of second operation command
enabled
33: One shot PLC
34: Proximity sensor input for simple Index
function
35: Output shutoff stop (NO)
36: Output shutoff stop (NC)
1 to 20 (*2ms)
01
0.00~200.00 %
0.00
00: Positive bias
00
01: Negative bias
01 to 200 %
100
00: No ACI negative bias command
01: Negative bias: REV motion enabled
00
02: Negative bias: REV motion disabled
0.00~200.00 %
0.00
00: Positive bias
01: Negative bias
00
01 to 200 %
100
00: No AUI negative bias command
01: Negative bias: REV motion enabled
00
02: Negative bias: REV motion disabled
0.00 to 10.00 sec
0.05
0.00 to 10.00 sec
0.05
0.00 to 10.00 sec
0.05
00: 0.01Hz
01
01: 0.1Hz
4 ~ 1000
200
0.0 ~360.0o
180.0
0.00 ~100.00 sec
0.00
Revision July 2008, BE16, SW V4.08 & V5.00