Chapter 5 Parameters|VFD-B Series
5.1 Summary of Parameter Settings
: The parameter can be set during operation.
Group 0 User Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
00-00 Identity Code of Read-only
##
the AC motor drive
00-01 Rated Current
Read-only
#.#
Display of the AC
motor drive
08: Keypad lock
09: All parameters are reset to factory settings
00-02 Parameter Reset
(50Hz, 220V/380V/575V)
00
10: All parameters are reset to factory settings
(60Hz, 220V/440V/575V)
00: Display the frequency command value (LED
F)
00-03
Start-up Display
Selection
01: Display the actual output frequency (LED H)
02: Display the content of user-defined unit
00
(LED U)
03: Multifunction display, see Pr.00-04
04: FWD/REV command
00: Display output current (A)
01: Display counter value (C)
02: Display process operation (1.tt)
03: Display DC-BUS voltage ( u )
04: Display output voltage (E)
05: Output power factor angle (n)
06: Display output power (P)
00-04
Content of Multi
Function Display
07: Display actual motor speed (HU)
08: Display the estimated value of torque as it
00
relates to current (t)
09: Display PG numbers/10ms (G)
10: Display analog feedback signal value (b)(%)
11: Display AVI (U1.) (%)
12: Display ACI (U2.) (%)
13: Display AUI (U3.) (%)
14: Display the temperature of heat sink (°C)
00-05
User-Defined
Coefficient K
0.01 to 160.00
1.00
00-06 Software Version Read-only
#.##
00-07 Password Input 00 to 65535
00
00-08 Password Set
00 to 65535
00
00: V/f Control
00-09 Control Method
01: V/f + PG Control
00
02: Vector Control
03: Vector + PG Control
5-2
Revision July 2008, BE16, SW V4.08 & V5.00