Chapter 2 Installation and Wiring|VFD-B Series
Terminal
Symbol
Terminal Function
Factory Settings (SINK)
ON: Connect to DCM
AFM
Analog output meter
ACM circuit
AFM
0~10V
potentiometer
Max. 2mA
internal circuit ACM
0 to 10V, 2mA
Impedance:
Output current
Resolution:
Range:
Function:
470
2mA max
8 bits
0 ~ 10VDC
Pr.03-05
ACM
Analog control signal
(common)
Common for AVI, ACI, AUI, AFM
Control signal wiring size: 18 AWG (0.75 mm2) with shielded wire.
Analog input terminals (AVI, ACI, AUI, ACM)
„ Analog input signals are easily affected by external noise. Use shielded wiring and keep it as
short as possible (<20m) with proper grounding. If the noise is inductive, connecting the
shield to terminal ACM can bring improvement.
„ If the analog input signals are affected by noise from the AC motor drive, please connect a
capacitor and ferrite core as indicated in the following diagrams:
C
ferrite core
AV I / A CI / A U I
ACM
wind each wires 3 times or more around the core
Digital inputs (FWD, REV, JOG, EF, TRG, MI1~MI6, DCM)
„ When using contacts or switches to control the digital inputs, please use high quality
components to avoid contact bounce.
Digital outputs (MO1, MO2, MO3, MCM)
„ Make sure to connect the digital outputs to the right polarity, see wiring diagrams.
„ When connecting a relay to the digital outputs, connect a surge absorber or fly-back diode
across the coil and check the polarity.
2-24
Revision July 2008, BE16, SW V4.08 & V5.00