Terminal
Symbol
Terminal Function
MO1
Multi-function Output 1
(Photocoupler)
MO2
Multi-function Output 2
(Photocoupler)
Chapter 2 Installation and Wiring|VFD-B Series
Factory Settings (SINK)
ON: Connect to DCM
Maximum 48VDC, 50mA
Refer to Pr.03-01 to Pr.03-03 for programming
MO1~MO3-DCM
Max: 48Vdc
50mA
MO1~MO3
MO3
Multi-function Output 3
(Photocoupler)
MCM
Internal Circuit
MCM Multi-function output common Common for Multi-function Outputs
+10V Potentiometer power supply +10VDC 20mA
Analog voltage Input
+10V
AVI circuit
Impedance:
Resolution:
Range:
AVI
AVI
ACM
internal circuit
Selection:
Set-up:
47k
10 bits
0 ~ 10VDC =
0 ~ Max. Output
Frequency (Pr.01-00)
Pr.02-00, Pr.02-13,
Pr.10-00
Pr.04-00 ~ Pr.04-03
Analog current Input
ACI circuit
ACI
ACI
Impedance:
Resolution:
Range:
Selection:
ACM internal circuit
Set-up:
Auxiliary analog voltage input
+10
~
-10V
AUI circuit
Impedance:
Resolution:
Range:
AUI
AUI
ACM
internal circuit
Selection:
Set-up:
250
10 bits
4 ~ 20mA =
0 ~ Max. Output
Frequency (Pr.01-00)
Pr.02-00, Pr.02-13,
Pr.10-00
Pr.04-11 ~ Pr.04-14
47k
10 bits
-10 ~ +10VDC =
0 ~ Max. Output
Frequency (Pr.01-00)
Pr.02-00, Pr.02-13,
Pr.10-00
Pr.04-15 ~ Pr.04-18
Revision July 2008, BE16, SW V4.08 & V5.00
2-23