Appendix C How to Select the Right AC Motor Drive|VFD-B Series
The requirement of load capacity should be less than the capacity of AC
motor drive(kVA)
The requirement of load capacity=
k × PM ≤ the _ capacity _ of _ AC _ motor _ drive(kVA)
η × cosϕ
The motor capacity should be less than the capacity of AC motor drive
k × 3 ×VM × IM ×10−3 ≤ the _ capacity_ of _ AC _ motor _ drive(kVA)
The current should be less than the rated current of AC motor drive(A)
k × IM ≤ the _ rated _ current _ of _ AC _ motor _ drive( A)
Symbol explanation
P M
: Motor shaft output for load (kW)
η
: Motor efficiency (normally, approx. 0.85)
cosϕ : Motor power factor (normally, approx. 0.75)
V M
: Motor rated voltage(V)
I M
: Motor rated current(A), for commercial power
k
: Correction factor calculated from current distortion factor (1.05 - 1.1, depending
on PWM method)
PC1
: Continuous motor capacity (kVA)
k S
: Starting current/rated current of motor
n T
: Number of motors in parallel
n S
: Number of simultaneously started motors
GD 2
: Total inertia (GD2) calculated back to motor shaft (kg m2)
T L
: Load torque
t A
: Motor acceleration time
N
: Motor speed
Revision July 2008, BE16, SW V4.08 & V5.00
C-3