Appendix B Accessories|VFD-B Series
Correct wiring
power
silicon rectifier
reactor
DC
reactor
AC motor drive
motor
Application 3
Question
Used to improve the input power factor, to When power capacity is too large, line
reduce harmonics and provide protection from impedance will be small and the charge
AC line disturbances. (surges, switching
current will be too large. That may damage
spikes, short interruptions, etc.). AC line
AC motor drive due to higher rectifier
reactor should be installed when the power temperature.
supply capacity is 500kVA or more and
exceeds 6 times the inverter capacity, or the
mains wiring distance 10m.
Correct wiring
large-capacity
power
reactor
small-capacity
AC motor drive
motor