kW
18.5
HP
Fundamental
Amps
Max.
continuous
Amps
25
25
37.5
Appendix B Accessories|VFD-B Series
Inductance (mH)
3% impedance 5% impedance
1.2
1.8
22
30
35
52.5
0.8
1.2
30
40
45
67.5
0.7
1.2
37
50
55
82.5
0.5
0.85
45
60
80
120
0.4
0.7
55
75
80
120
0.4
0.7
75 100
100
150
0.3
0.45
B.6.3 Applications for AC Reactor
Connected in input circuit
Application 1
Question
When more than one AC motor drive is
connected to the same power, one of them is
ON during operation.
Correct wiring
M1 reactor
When applying to one of the AC motor drive,
the charge current of capacity may cause
voltage ripple. The AC motor drive may
damage when over current occurs during
operation.
AC motor drive
motor
M2
AC motor drive
motor
Mn
Application 2
Silicon rectifier and AC motor drive is
connected to the same power.
AC motor drive
motor
Question
Surges will be generated at the instant of
silicon rectifier switching on/off. These surges
may damage the mains circuit.
Revision July 2008, BE16, SW V4.08 & V5.00
B-35