575V, 50/60Hz, 3-Phase
Appendix B Accessories|VFD-B Series
kW
HP
Fundamental
Amps
Max.
continuous
Amps
Inductance (mH)
3% impedance 5% impedance
0.75
1
2
3
20
32
1.5
2
4
6
9
12
2.2
3
4
6
9
12
3.7
5
8
12
5
7.5
5.5
7.5
8
12
3
5
7.5
10
12
18
2.5
4.2
11
15
18
27
1.5
2.5
15
20
25
37.5
1.2
1.8
18.5 25
25
37.5
1.2
1.8
22
30
35
52.5
0.8
1.2
30
40
45
67.5
0.7
1.2
37
50
55
82.5
0.5
0.85
45
60
80
120
0.4
0.7
55
75
80
120
0.4
0.7
75 100
100
150
0.3
0.45
B.6.2 AC Output Reactor Recommended Value
230V, 50/60Hz, 3-Phase
kW
HP
Fundamental
Amps
0.75
1
8
Max.
continuous
Amps
12
Inductance (mH)
3% impedance 5% impedance
3
5
1.5
2
8
12
1.5
3
2.2
3
12
18
1.25
2.5
3.7
5
18
27
0.8
1.5
5.5 7.5
25
37.5
0.5
1.2
7.5
10
35
52.5
0.4
0.8
11
15
55
82.5
0.25
0.5
15
20
80
120
0.2
0.4
18.5 25
80
120
0.2
0.4
22
30
100
150
0.15
0.3
30
40
130
195
0.1
0.2
37
50
160
240
0.075
0.15
Revision July 2008, BE16, SW V4.08 & V5.00