Appendix B Accessories|VFD-B Series
2. Connect Externally with the Encoder of 12V Power Supply and Output Signals to
Additional Tachometer
R/L1
Non-Fuse Breaker
NFB
R/L1
U/T1
S/L2
S/L2
V/T2
M
3~
T/L3
T/L3
W/T3
VFD-B
A
A
PG-03
B
B
A
A
B PG
B
OC
12V
0V
GND
TP
*Specification of the
A/O
Encoder is of 12V/OC output,
which could also connect
B/O
externally with the RPM wire
Shield 0V
Terminal
RPM Meter
*Power of the RPM meter should
be supplied by the customers
Main circuit (power) terminals
Control circuit terminals
Connection between PG-03 and the Encoder
B.3.2.3 PG-03 Terminal Descriptions
1. Terminals
Terminal Symbols
Descriptions
+12V
Power Supply of the Encoder: +12V
Output Voltage: +12V±5% 200mA
0V
A- A B- B
A/O, B/O
Common point for the power supply and the signal
Input signal from Pulse Generator. Input type is selected by FSW2. It
can be 1-phase or 2-phase input. Maximum 500kP/sec (z-phase
function is reserved). If the voltage exceeds 12V, it needs to use TP
type with connecting the external current limiting resistor(R). The
current should be within 5 to 15mA.
The formal of current limiting resistor is:
5mA Vin 2V 15mA
600Ω + R
The Encoder signal output
Maximum: DC24V 300mA
Common point for signal grounding
2. Wiring Notes
Revision July 2008, BE16, SW V4.08 & V5.00