Chapter 8 Maintenance and Inspections|VFD-B Series
DC capacity of main circuit
Check Items
Methods and Criterion
If there is any leak of liquid,
color change, crack or
deformation
Measure static capacity when
required
Visual inspection
Static capacity ≥ initial value X 0.85
Maintenance
Period
Daily
Half
Year
One
Year
{
{
Resistor of main circuit
Check Items
Methods and Criterion
Maintenance
Period
Daily
Half
Year
One
Year
If there is any peculiar smell or
insulator cracks due to overheat
Visual inspection, smell
{
Visual inspection or measure with
If there is any disconnection
multimeter after removing wiring
between +1/+2 ~ -
{
Resistor value should be within ± 10%
Transformer and reactor of main circuit
Check Items
Methods and Criterion
If there is any abnormal vibration
or peculiar smell
Visual, aural inspection and smell
Maintenance
Period
Daily
Half
Year
One
Year
{
Magnetic contactor and relay of main circuit
Check Items
Methods and Criterion
If there are any loose screws
Check to see if contacts work
correctly
Visual and aural inspection
Visual inspection
Maintenance
Period
Daily
Half
Year
One
Year
{
{
8-4
Revision July 2008, BE16, SW V4.08 & V5.00