Chapter 7 Troubleshooting |VFD-B Series
7.11 Motor Stalls during Acceleration
Motor stalls during
acceleration
Check if acceleration Yes
time is too short
No
Check if the inertia Yes
of the motor and load
is too high
No
Thicken or shorten the
wiring between the
motor or AC motor drive
Yes
Check for low voltage
at input
No
Reduce load or
increase the capacity
of AC motor drive
Yes Check if the load torque
is too high
No
Check if the torque
Yes
compensation is suitable
No
Increase setting time
Yes
Use special motor?
No
Reduce load or
increase the capacity
of AC motor drive
Maybe AC motor drive has
malfunction or misoperation
due to noise. Please contact
DELTA
Increase torque compensation
7.12 The Motor does not Run as Expected
Motor does not run
as expected
Check Pr. 01-01 thru Pr. 01-06
and torque compensation
settings
No
Adjust Pr.01-01 to Pr.01-06
and lower torque compensation
Yes
Run in low speed continuously Yes
No
Is load too large Yes
No
Please use specific motor
Reduce load or increase the
capacity of AC motor drive
Check if output voltage of U, V, W Yes
is balanced
No
Motor has malfunction
Maybe AC motor drive has malfunction or misoperation
due to noise. Please contact DELTA.
7-8
Revision July 2008, BE16, SW V4.08 & V5.00