7.10 Motor Speed cannot be Changed
Motor can run but
cannot change speed
Chapter 7 Troubleshooting |VFD-B Series
Modify the setting
Yes
If the setting of
Pr.05-17toPr.05-31
Yes is too high
No
Yes If finished with
executing
Pr.05-15
No
Yes Check if the setting of the
max. frequency is too low
No
Check to see if frequency is
out of range (upper/lower)
Yes
boundaries
No
Yes Is it in PLC mode No
Yes If the setting of
Pr.05-00 to Pr.05-14
are the same
Modify the setting
Press UP/DOWN key
to see if speed has
Yes
any change
If there is any change
of the signal that sets Yes
frequency (0-10V and
4-20mA)
No
Check if the wiring between
No
M1~M6 to DCM is correct
Yes
No
No Check if the wiring of
external terminal is correct
Check if frequency for
each step is different
Correct
wiring
No
Yes
Change defective
potentiometer
Yes
No Check if accel./decel.
time is set correctly
Change frequencysetting
Yes
Please set suitable
accel./decel. time by
load inertia
Maybe AC motor drive has malfunction or misoperation
due to noise. Please contact DELTA.
Revision July 2008, BE16, SW V4.08 & V5.00