7.4 Low Voltage (Lv)
Low voltage
Chapter 7 Troubleshooting |VFD-B Series
Is input power correct? Or power cut, Yes
including momentary power loss
No
Restart after reset
Check if there is any malfunction Yes
component or disconnection in
power supply circuit
No
Change defective component
and check connection
Check if voltage is
No
within specification
Yes
Make necessary corrections,
such as change power supply
system for requirement
Check if there is heavy load Yes Using the different power
with high start current in the
supply for this drive and
same power system
heavy load system
No
Check if Lv occurs when Yes
breaker and magnetic
contactor is ON
No
Check if voltage between +1/+2
and - is greater than
No
200VDC (for 230V models)
400VDC (for 460V models)
517VDC (for 575V models)
Yes
No
Suitable power
transformer capacity
Yes
Maybe AC motor drive has malfunction.
Please contact DELTA.
Control circuit has malfunction or
misoperation due to noise. Please
contact DELTA.