Chapter 7 Troubleshooting |VFD-B Series
7.2 Ground Fault
GFF
Ground fault
Is output circuit(cable or No
motor) of AC motor drive
grounded?
Yes
Maybe AC motor drive has
malfunction or misoperation
due to noise. Please
contact DELTA.
Remove ground fault
7.3 Over Voltage (OV)
Over voltage
Reduce voltage to
be within spec.
No Is voltage within
specification
Yes
Maybe AC motor drive
has malfunction or
misoperation due to
noise. Please contact
DELTA.
Has over-voltage occurred without load Yes
No
No When OV occurs, check if the
voltage of DC BUS is greater
than protection value
Yes
Yes
No Dose OV occur when
sudden acceleration
stops
Yes
Increase
deceleration
Yes
time
No
Reduce moment
of inertia
Increase
Yes
acceleration
time
Increase setting time
No
No
Reduce moment of load inertia
Need to consider using
brake unit or
DC brake
No
Use brake unit or DC brake
No
Yes
Need to check control method. Please contact DELTA.
7-2