11 - 05 Sleep/Wake Up Detection Time
Settings
0.0 to 6550.0 sec
Chapter 5 Parameters|VFD-B Series
Unit: 0.1
Factory Setting: 0.0
11 - 06 Sleep Frequency
Unit: 0.01
Settings
0.00 to Fmax Hz
Factory Setting: 0.00
11 - 07 Wakeup Frequency
Unit: 0.01
Settings
0.00 to Fmax Hz
Factory Setting: 0.00
When the actual output frequency Pr.11-06 and the time exceeds the setting of Pr.11-05,
the AC motor drive will be in sleep mode.
When the actual frequency command > Pr.11-07 and the time exceeds the setting of Pr.11-05,
the AC motor drive will restart.
When the AC motor drive is in sleep mode, frequency command is still calculated by PID.
When frequency reaches wake up frequency, AC motor drive will accelerate from Pr.01-05 min.
frequency by V/f curve.
The wake up frequency must be higher than sleep frequency.
Frequency
frequency calculated by PID
11-07
11-06
01-08
01-05
The limit of
decel. time
output
frequency
The limit of
accel. time
11-05
Time
Fmin
lower bound
of frequency
Fsleep
Fcmd=0
Fout = 0
Fmin<Fsleep<
lower bound
of frequency